Heat recovery analysis of a fixed plate energy recovery ventilator

Adams Moro Patricia Kwakye-Boateng

Abstrak

Abstract As building becomes more leak-tight, air refreshment to improve indoor air quality is needed for healthy living standards. In the quest to ensure comfortable indoor climatic conditions, energy recovery ventilators (ERV) are used to provide air refreshment and thermal comfort. In this study, a fixed plate air-to-air ERV was analysed to determine its effectivity in terms of energy recovery during air refreshment. A customized test bench was built and used to acquire the instantaneous surface temperatures of the heat exchanger plates contained in the ERV during air refreshment. Also, a numerical model of the ERV was developed and validated by comparing its output from simulation with experiment results under the same conditions. The model consisted of a single heat exchanger plate and the air across the plate surface. To capture the effect of heat transfer between the air and the heat exchanger plate in 3D, the model was discretized into numerous cells. From the experiment and simulation results, the air-to-air ERVs were more effective in recovering thermal energy at low flow velocity than at high flow velocity. At lower flow velocity, it will take a longer time duration before any significant impact is made on the thermal conditions of the building, comparatively. The prediction of the model was within acceptable margins and could be used to provide insight on the ERVs performance improvement.

Penulis (2)

A

Adams Moro

P

Patricia Kwakye-Boateng

Format Sitasi

Moro, A., Kwakye-Boateng, P. (2024). Heat recovery analysis of a fixed plate energy recovery ventilator. https://doi.org/10.1186/s40807-024-00122-2

Akses Cepat

PDF tidak tersedia langsung

Cek di sumber asli →
Lihat di Sumber doi.org/10.1186/s40807-024-00122-2
Informasi Jurnal
Tahun Terbit
2024
Sumber Database
DOAJ
DOI
10.1186/s40807-024-00122-2
Akses
Open Access ✓