Implementation and laboratory verification of method utilizing phase and neutral quantities for detection and location of low‐current earth faults in resonant grounded networks

Thomas Treider Hans Kristian Høidalen

Abstrak

Abstract Earth faults is a challenging fault type to locate in resonant grounded networks due to their naturally low fault current, and the problem increases with an increased fault impedance. This paper describes the detailed implementation and laboratory testing of a method for detection, location and clearing of earth faults with very small fault currents. The method consists of two indicators used in the fault detection stage, where their simultaneous operation ensures selective fault detection and faulty feeder selection. One of these indicators also enables continuous fault indication throughout a sectionalizing process. The laboratory tests demonstrate that both indicators function as intended, and it is the current sensors which ultimately limit the attainable sensitivity. Faults up to 15 kΩ were detected successfully in the laboratory network based on phase current measurements, while the sectionalizing indicator showed much higher sensitivity and functioned as intended in a 50 kΩ fault. Measurements from one field test in a 22 kV network corroborate the laboratory results and demonstrate the expected earth fault indicator response.

Penulis (2)

T

Thomas Treider

H

Hans Kristian Høidalen

Format Sitasi

Treider, T., Høidalen, H.K. (2023). Implementation and laboratory verification of method utilizing phase and neutral quantities for detection and location of low‐current earth faults in resonant grounded networks. https://doi.org/10.1049/gtd2.13059

Akses Cepat

PDF tidak tersedia langsung

Cek di sumber asli →
Lihat di Sumber doi.org/10.1049/gtd2.13059
Informasi Jurnal
Tahun Terbit
2023
Sumber Database
DOAJ
DOI
10.1049/gtd2.13059
Akses
Open Access ✓