DOAJ Open Access 2023

Evolution of grounding failure‐insulation failure of 10 kV cable joints: Prerequisites of an explosion in enclosed cable trench

Yifeng Zhao Gang Liu Yaodong Guo Chenglong Huang Zhaoming He +1 lainnya

Abstrak

Abstract An explosion accident in an enclosed cable trench caused by the discharge of 10 kV three‐phase cable joints is discussed. Combined with the disassembly analysis, the fault recording data analysis, and the validation of experiment, the evolution of the cable joint fault is deduced and discussed. The results show that the trigger of the cable joint fault is the creepage discharge at the cross‐linked polyethylene–silicon rubber insulation interface. This results in the partial breakdown and the grounding failure of three‐phase cable joints. Under the long‐term floating potential and current thermal effect, the insulations are gradually ablated and decomposed into a large amount of combustible gas. Finally, the accumulated combustible gas is ignited by the arc caused by a three‐phase short circuit at the moment of the reclosing operation. The analytical method and conclusions proposed in this paper can provide suggestions and guidance to prevent analogous distribution network cable joint fault accidents.

Penulis (6)

Y

Yifeng Zhao

G

Gang Liu

Y

Yaodong Guo

C

Chenglong Huang

Z

Zhaoming He

R

Ran Hu

Format Sitasi

Zhao, Y., Liu, G., Guo, Y., Huang, C., He, Z., Hu, R. (2023). Evolution of grounding failure‐insulation failure of 10 kV cable joints: Prerequisites of an explosion in enclosed cable trench. https://doi.org/10.1049/gtd2.12905

Akses Cepat

PDF tidak tersedia langsung

Cek di sumber asli →
Lihat di Sumber doi.org/10.1049/gtd2.12905
Informasi Jurnal
Tahun Terbit
2023
Sumber Database
DOAJ
DOI
10.1049/gtd2.12905
Akses
Open Access ✓